BRAND : Gestra
Technical Data
Service pressure PN25: 25 barg at 224 °C Mechanical connection Screwed ¾", ISO 228-1 Screwed ¾" NPT (optional) Materials Screw-in electrode body: 1.4571, X6CrNiMoTi17-12-2 or 1.4404, A 479 316 L (for NPT thread) Measuring electrode: 1.4571, X6CrNiMoTi17-12-2 Electrode rod insulation: PTFE Terminal box: Polycarbonate Measuring length & length of installation 200, 300, 400, 500, 600, 800, 1000 mm Input 1 Input for resistance thermometer, e. g. TRG 5-53, measuring insert Pt 100 Measuring range 100 to 10000 µS/cm at 25 °C or 50 to 5000 ppm at 25 °C Setpoint Adjustable between 100 and 10000 µS/cm or 50 to 5000 ppm MAX limit Adjustable between 100 and 10000 µS/cm or 50 to 5000 ppm Switching hysteresis Controller output: –10 % of the adjusted setpoint MAX limit: –3 % of the adjusted MAX limit
Temperature coefficient Tk (if a resistance thermometer Pt 100 is connected) 1.6 – 3.0 % per °C, adjustable in steps of 0.1 Supply voltages 230 V, +10 / –15 %, 50-60 Hz 115 V, +10 / –15 %, 50-60 Hz (optional) Power consumption 5 VA Fuse External slow-blow fuse 63 mA at 230 V External slow-blow fuse 125 mA at 115 V Output 3 Volt-free relay contacts 5 A 230 V AC / 30 V DC cos ? = 1 (IEC 61810) Provide contactor with inference suppressor (RC combination). Contact material: AgNi 0.15 Indicators and adjustors 1 Four-digit, seven-segment indicator, red, for showing the actual value (X) / setpoint (W) and status &am...
Technical Data
Service pressure PN25: 25 barg at 224 °C Mechanical connection Screwed ¾", ISO 228-1 Screwed ¾" NPT (optional) Materials Screw-in electrode body: 1.4571, X6CrNiMoTi17-12-2 or 1.4404, A 479 316 L (for NPT thread) Measuring electrode: 1.4571, X6CrNiMoTi17-12-2 Electrode rod insulation: PTFE Terminal box: Polycarbonate Measuring length & length of installation 200, 300, 400, 500, 600, 800, 1000 mm Input 1 Input for resistance thermometer, e. g. TRG 5-53, measuring insert Pt 100 Measuring range 100 to 10000 µS/cm at 25 °C or 50 to 5000 ppm at 25 °C Setpoint Adjustable between 100 and 10000 µS/cm or 50 to 5000 ppm MAX limit Adjustable between 100 and 10000 µS/cm or 50 to 5000 ppm Switching hysteresis Controller output: –10 % of the adjusted setpoint MAX limit: –3 % of the adjusted MAX limit
Temperature coefficient Tk
(if a resistance thermometer Pt 100 is connected)
1.6 – 3.0 % per °C, adjustable in steps of 0.1
Supply voltages
230 V, +10 / –15 %, 50-60 Hz
115 V, +10 / –15 %, 50-60 Hz (optional)
Power consumption
5 VA
Fuse
External slow-blow fuse 63 mA at 230 V
External slow-blow fuse 125 mA at 115 V
Output
3 Volt-free relay contacts
5 A 230 V AC / 30 V DC cos ? = 1 (IEC 61810)
Provide contactor with inference suppressor
(RC combination).
Contact material: AgNi 0.15
Indicators and adjustors
1 Four-digit, seven-segment indicator, red, for showing the
actual value (X) / setpoint (W) and status & malfunction
messages
2 Amber LEDs for indicating the actual value (X) /
setpoint (W)
1 Red LED for indicating the MAX limit
2 Green LEDs for indicating “Valve OPEN / CLOSED”
4 Pushbuttons for parameter settings
Cable entry / Electrical connection
Cable glands with integrated cable clamp,
3 x M 16 x 1.5
1 Four-pole screw-type terminal strip for mains connection
1 Three-pole screw-type terminal strip for connecting the
continuous blowdown valve
1 Three-pole screw-type terminal strip for MAX limit
The terminal strips can be detached;
conductor size 1.5 mm2
4 Terminal lugs for connecting the resistance thermometer
Protection
IP 65 to DIN EN 60529
Protection class
2 (protective insulation)
Weight
Approx. 1.5 kg
Ambient temperature
when system is switched on: 0 ° ... 70 °C,
during operation: -10 ... 70 °C
Transport temperature
–20 ... +80 °C (< 100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours.
Storage temperature
–20 ... +70 °C, defrosting time of the de-energized equipment
before it can be put into operation: 24 hours.
Relative humidity
max. 95%, no moisture condensation
Site altitude
max. 2000 m