BRAND : Ziehl
Power Supply
Rated supply voltage Us
AC/DC 24 – 240V
Tolerance
DC 20,4 - 297 V,
AC 20 - 264 V 50/60 Hz
Power consumption
< 4 W
< 13 VA
Sensor connection (6 sensors)
Pt 100 (RTD) acc. to EN 60751 (2/3- wire)
Measuring range
-199°C .. 800°C, resolution = 1°C
Resistance of sensor + wire.
max. 500 Ohm
Sensor current
?0,7 mA
Measuring cycle/ time sensor
? 1,5 s
Tolerance
±0,5 % of measured value ±1 digit
Temperature factor
<0,04°C/K
K1 … K7
7 x 1 change-over contacts (CO)
Switching voltage
max. AC 415 V
Switching current
max. 5 A
Switching capacity
max. 1250 VA (resistive load)
max. 120 W at DC 24 V
UL electrical ratings
250 V ac, 5 A, resistive
E214025
240 V ac, 1/2 hp
120 V ac, ¼ hp
B 300 – pilot duty, UL 508
Nominal operational current Ie
AC15
Ie = 3 A ..... Ue = 250 V
DC13
Ie = 2 A ..... Ue = 24 V
Ie = 0,2 ..... A Ue = 125 V
Ie = 0,1 ..... A Ue = 250 V
Recommended fuse NO
4 A time-lag or miniature circuit-breaker MCB B4
Recommended fuse NC
3.15 A time-lag
Expected contact life mechanical
3 x 107 operations
Expected contact life electrical
1 x 105 operations at AC 250 V / 6 A