BRAND : Ziehl
Control voltage Us
AC/DC 24 – 240 V, 0/50/60 Hz, <2 W < 4 VA
Limits
Control voltage Us
AC/DC 24 – 240 V, 0/50/60 Hz, <2 W < 4 VA
Limits
DC 20.4 - 297 V
AC 20 - 264 V
Sensor connection
Pt 100 according to EN 60751 (2/3-wire version)
Measuring range
-199°C. 850°C / -199°F .. 999°F
Sensor resistance + line res.
max. 500 Ohm
Sensor current
? 0.7 mA
Measurement cycle/measurement time
< 2.5 s
Tolerance
± 1°C, ± 1 Digit
Temperature drift
<0.04°C/K
Relay data K2, K3 and K4
3 x 1 change-over contact
Switching voltage
max. AC 415 V
Switching current
max. 6 A
Switching capacity
max. 2000 VA (Ohmic load)
max. 120 W at DC 24 V
Nominal operating current for reversing switch
3 A AC15 250 V; 2 A DC13 24 V
Recommended series fuse
3.15 A slow-to-blow ( gL )
Contact service life, mechanical
3 x 107 operating cycles
Contact service life, electrical
1 x 105 operating cycles at 240 V / 6 A
Reduction factor at cos ? 0,3
0,5