What are you looking for?

Varec 8130 Remote Terminal Unit

BRAND : Varec

The 8130 Remote Terminal Unit (RTU) collects and transmits data from field instruments to a central system, such as FuelsManager®The 8130 Remote Terminal Unit (RTU) collects and transmits data from field instruments to a central system, such as FuelsManager®, host DCS or PLCs. All information obtained can be used for inventory, alarm, control and automation.

Specifications

Power

Supply – 110–120 V AC or 200–240 V AC @ 50/60 Hz or 18–36 V DC
Consumption – 50 VA max @ 110/220 VAC (500 mA), 20 VA max @ 24 VDC

Operating Temperature Range

?40 to +158 °F (?40 to +70 °C)

Approvals

FM ? Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required)
CSA ? Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)



Options

01 Power Supply

  • 110…120 V AC 50/60 Hz
  • 220…240 V AC 50/60 Hz
  • 18…36 V DC

02 Host Emulation

  • None
  • TSU Emulation ? for connection to Varec TankView systems
  • CIU Emulation ? emulates Enraf model 858 CIU interface

03 Field Communications

  • None
  • Varec Matrix Communication ? interfaces to Varec Matrix devices (1600/1700) require 8210, 8201 & 8204 Interface Modules
  • MODBUS Master Communication*
  • CIU communication ? interfaces to existing Enraf 858 CIU devices*
  • Veeder Root (TLS 350) Communication*
  • Hectronic OptiLevel Communication*

Note! * Using RTU motherboard communications ports

04 Calculations

  • None
  • Hybrid tank calculations
  • Hydrostatic tank calculations

05 Strapping Tables

  • None
  • Embedded tank strapping tables
  • Floating Roof Tank with Floatwell
  • Tank Top Mounting
  • Bolted Tank
  • Cone Roof Tank with Pan (No Floatwell)
  • Floating Roof Tank (No Floatwell

06 Approvals

  • For use in non?hazardous areas
  • FM ? Class I, Division 2, Groups A, B, C & D T3C (with optional NEMA 4 enclosure required)
  • CSA ? Class I, Division 2, Groups A, B, C & D (with optional NEMA 4 enclosure required)

INTERFACE MODULES

16-Channel Digital I/O

Interface Module 8201

  • 16 digital I/O channels
  • 24 VDC, 120 or 240 VAC
  • Channels individually configurable for input or output
  • Dedicated status LED
  • Dedicated fuse for output modules only
  • Requires two I/O expansion module slots

MODBUS Dual RS-485

Interface Module 8203

  • Dual high-speed communications channels
  • Optically isolated
  • Up to 32 devices per channel
  • Communications with instruments using Rackbus, MODBUS, DDA, or Petrosense Probe protocols
  • Requires one I/O expansion module slot

8 Channel Multi-Function

Interface Module 8204

  • Isolated analog (4-20 mA), Thermocouple, RTD inputs, high speed pulse accumulation or digital I/O channels
  • 24 VDC, 120 or 240 VAC operation
  • Individually configurable for input or output
  • Dedicated status LED/fuses
  • Requires one I/O expansion module slot

16 Channel Analog Input

Interface Module 8205

  • 12 bit accuracy A/D with common-mode noise rejection
  • Dedicated fused 24V line for each channel
  • Throughput accuracy (field to database) = ±0.012%.
  • Each channel individually configurable for; 4-20 mA loop powered input, 4-20 mA self powered, voltage input
  • Requires two I/O expansion module slots

8-Channel Analog Output

Interface Module 8207

  • 16 Bit accuracy D/A converter
  • Current or voltage level output (0-24 mA, 0-20 mA, 4-20 mA & 0-5V)
  • 8 channels
  • Requires one I/O expansion module slot

TIWAY (Texas Inst.)

Interface Module 8208

  • Dual high-speed communications channels
  • Optically isolated
  • Up to 32 devices per channel
  • Communications using TIWAY or CIM protocol
  • Requires one I/O expansion module slot

Mark/Space (Varec)

Interface Module 8210

  • Supports up to 50 tanks
  • Communicates using Mark/Space protocol
  • Interfaces to the Varec 1900 and compatible tank gauge transmitters
  • Requires one I/O expansion module slot

Current Loop

Interface Module 8211

  • 20 mA current loop
  • Up to 15 devices per channel
  • Two channels
  • Communicates using GPE or Whessoe Bus protocol
  • Requires one I/O expansion module slot

TRL/2 (SAAB)

Interface Module 8212

  • Saab (Emmerson) TRL/2 Bus
  • Up to 16 Saab Radar Tank Gauges per channel
  • Two channels
  • Requires one I/O expansion module slot

BPM (Enraf)

Interface Module 8214

  • Transformer isolated
  • Up to 10 tanks per channel
  • Two channels
  • Communications with Enraf tank gauges
  • Requires one I/O expansion module slot

Tankway (L&J)

Interface Module 8215

  • Supports up to 50 tanks
  • Communicates using L&J Tankway protocol
  • Interfaces to L&J Tankway compatible tank gauge transmitters
  • Requires one I/O expansion module slot

LON (Prime/Barton)

Interface Module 8216

  • Supports up to 128 tanks
  • Communicates with LON Series 3500 TCU
  • 78 Kbps twisted pair LON interface
  • Requires one I/O expansion module slot

Dual RS-232

Interface Module 8217

  • Dual high-speed communications channels
  • RS-232 communications
  • Communicates with L&J Model 8100
  • Communicates with Veeder Root TLS-350
  • Communicates with Universal Sensors & Devices CATLAS
  • Communicates with Enraf CIU
  • Communicates with MODBUS devices
  • Requires one I/O expansion module slot



01 Power Supply

Other Suggested Products

Products