What are you looking for?

Holthausen Mini-C (hol551)

BRAND : Holthausen

Details

DESCRIPTION:

The ESW® -Mini-C is used for permanent machine monitoring and corresponds at this technical execution to performance level PL-c.

Unwanted vibrations,which occur through mechanical defects or imbalances, are detected at the monitored machines in time. Using the alarm relay,warning devices can be adressed.Thanks to the early detection, a rising wear and the associated costs is avoided and the life time is prolonged. Also production losses are reduced,whereby a higher planning security is guranteed.

Through the integrated sensor, a stabil Die-cast aluminum housing and the easy installation and handling of the ESW® -Mini-C, high reliability is guaranteed. The device can be manufactured with an analog output, which behaves proportional to the measurement range.

Performance-Level PL-c (acc. to EN13849) / category Cat.-2

Diagnostic coverage DC = low / mean time to dangerous failure MTTFd = high

APPLICATION FIELDS:

At all technical applications in which oscillations occur, the ESW® -Mini-C is a valuable support. Here are some examples:

  • Fan,pumps and air blower
  • shaker,decanter and separators
  • Conveying and transport equipment
  • Drives
  • Instrument, processing and production machines
TECHNICAL DATA:

Performance-Level PL-c (acc. to EN13849) category Cat.-2:

diagnostic coverage DC = low meantime to dangerous failure MTTFd = high

operating voltage:

24V DC 10%

current input:

max. 45mA

temparature range:

0°C bis +65°C

type of protection:

IP 65

case:

Aluminium pressure-die-casting

case dimensions:

98 x 34 x 64mm (w x h x d)

weight:

ca. 650g (with baseplate)

baseplate (optional):

aluminum baseplate 97 x 4 x 63mm with 19mm hexagonal bolt, M8 x 1,25 x 20mm, internal threat

connection cable:

different length and cable type, connected device side firmly

sensor:

integrated acceleration sensor

measuring value:

vibration acceleration in m/s2 or schwing speed in mm/s

measurement range:

0 bis 10g (1g = 9,81m/s2), or 0 bis 20mm/s, non-adjustable, or 0 bis 15mm/s, 0 to 30mm/s, 0 to 45mm/s, adjustable over DIP switch inside the case

signal assessment:

arithm. average, aligned to RMS

frequency range:

1Hz bis 100Hz or 3Hz to 30Hz or 5Hz to 1kHz or 10 to 1kHz (-3dB)

filter:

Butterworth, 40dB/dek or. 12dB/okt

analog output (optional):

0 to 20mA or 4 to 20mA, constant current proportional to the measurement range

switching output: