Multimode fiber (MM) 50/125 µm | 0 - 5000 m, 8 dB link budget at 1300 nm, A = 1 dB/km, 3 dB reserve, B = 800 MHz x km |
Multimode fiber (MM) 62.5/125 µm | 0 - 4000 m, 11 dB link budget at 1300 nm, A = 1 dB/km, 3 dB reserve, B = 500 MHz x km |
Power requirements |
Operating voltage | Power supply via the backplane of the MICE switch |
Power consumption | 7W |
Service |
Diagnostics | LEDs (power, link status, data, 100 Mbit/s, full duplex, ring port, LED test) |
Ambient conditions |
Standard operating temperature | 0 C to +60 C |
Optional operating temperature | -40 C to +70 C |
Storage/transport temperature | -40 C to +70 C |
Protective paint on PCB | optional |
Relative humidity (non-condensing) | 10% to 95% |
MTBF | 59.5 years; MIL-HDBK 217F: Gb 25 C |
Mechanical construction |
Dimensions (W x H x D) | 38 mm x 134 mm x 118 mm |
Mounting | Backplane |
Weight | 180 g |
Protection class | IP 20 |
Mechanical stability |
IEC 60068-2-27 shock | 15 g, 11 ms duration, 18 shocks |
IEC 60068-2-6 vibration | 1 mm, 2 Hz - 13.2 Hz, 90 min.; 0.7g, 13.2 Hz - 100 Hz, 90 min.; 3.5 mm, 3 Hz - 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10 cycles, 1 octave/min. |
EMC interference immunity |
EN 61000-4-2 electrostatic discharge (ESD) | 6 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 electromagnetic field | 10 V/m (80 - 1000 MHz) |
EN 61000-4-4 fast transients (burst) | 2 kV power line, 1 kV data line |
EN 61000-4-5 surge voltage | power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line |
EN 61000-4-6 conducted immunity | 3 V (10 kHz - 150 kHz), 10 V (150 kHz - 80 MHz) |
EMC emitted immunity |
FCC CFR47 Part 15 | FCC CFR47 Part 15 Class A |
EN 55022 | EN 55022 Class A |
Approvals |
Safety of industrial control equipment | cUL 508 |
Hazardous locations | ISA 12.12.01 Class 1 Div. 2 (pending) |
Shipbuilding | Germanischer Lloyd |
Scope of delivery and accessories |
Scope of delivery | module, operating manual |
Accessories to order separately | ML-MS2/MM labels |