More Interfaces |
Power supply/signaling contact | 1 plug-in terminal block, 3-pin, no signal contact |
Network size - Length of cable |
Twisted pair (TP) | 0 - 100 m |
Multimode Fiber (MM) 50/125 µm | 0 - 5000 m, 8 dB link budget at 1300 nm, A = 1 dB/km, 3 dB reserve, B = 800 MHz x km |
Multimode Fiber (MM) 62.5/125 µm | 0 - 4000 m, 11 dB Link budget at 1300 nm, A = 1 dB/km, 3 dB reserve, B = 500 MHz x km |
Network size - Cascadibility |
Line - / star topology | any |
Power requirements |
Operating voltage | 9.6 VDC - 32 VDC |
Current consumption at 24 V DC | max. 150 mA |
Power consumption | max. 3.9 W; 13.3 Btu(IT)/h at 24 VDC |
Service |
Diagnostics | LEDs (power, link status, data, data rate) |
Ambient conditions |
Operating temperature | -40 C to +70 C |
Storage/transport temperature | -40 C to +70 C |
Relative humidity (non-condensing) | 10% to 95% |
MTBF | 112 years, MIL-HDBK 217F: Gb 25 C |
Mechanical construction |
Dimensions (W x H x D) | 25 mm x 114mm x 79 mm |
Mounting | DIN Rail 35 mm |
Weight | 120 g |
Protection class | IP 30 |
Mechanical stability |
IEC 60068-2-27 shock | 15 g, 11 ms duration, 18 shocks |
IEC 60068-2-6 vibration | 3.5 mm, 3 Hz - 9 Hz, 10 cycles, 1 octave/min.; 1g, 9 Hz - 150 Hz, 10 cycles, 1 octave/min. |
EMC interference immunity |
EN 61000-4-2 electrostatic discharge (ESD) | 6 kV contact discharge, 8 kV air discharge |
EN 61000-4-3 electromagnetic field | 10 V/m (80 - 1000 MHz) |
EN 61000-4-4 fast transients (burst) | 2 kV power line, 4 kV data line |
EN 61000-4-5 surge voltage | power line: 2 kV (line/earth), 1 kV (line/line), 1 kV data line |
EN 61000-4-6 conducted immunity | 10 V (150 kHz - 80 kHz) |
EMC emitted immunity |
FCC CFR47 Part 15 | FCC CFR47 Part 15 Class A |
EN 55022 | EN 55022 Class A |
Scope of delivery and accessories |
Scope of delivery | device, terminal block, operating manual |
Accessories to order separately | Rail power supply RPS 15, RPS 30, RPS 80 EEC or RPS 120 EEC, 19" installation frame |