Barksdale Series 450 Intelligent Transmitter

BRAND : Barksdale

Barksdale Intelligent Transmitters (BiT), Series 450 is a high pressure transmitter with HART® communication protocol option. HART® enabled sensors can communicate over the legacy two-wire 4-20 mA analog current loops offering smart features like transmitter diagnostics, calibration, and field re-ranging up to 10 times less than calibrated full scale output (10:1 turndown ratio). Three models are available: Series H455, 4-20 mA output with HART® Comm. Protocol; Series 455, 4-20 mA output; Series 452, 1-5 VDC output. These models can be configured with 24-standard pressure ranges from vacuum to 30,000 psi and multiple process connections from 1/4” NPT to 7/16” SAE and HF4 Autoclave high-pressure connections. Multiple electrical connections are also offered, including popular industrial and MS style connectors for easy connection. Series 450 offers cULus approval for ordinary location.

General Specifications*

Details

Barksdale Intelligent Transmitters (BiT), Series 450 is a high pressure transmitter with HART® communication protocol option. HART® enabled sensors can communicate over the legacy two-wire 4-20 mA analog current loops offering smart features like transmitter diagnostics, calibration, and field re-ranging up to 10 times less than calibrated full scale output (10:1 turndown ratio). Three models are available: Series H455, 4-20 mA output with HART® Comm. Protocol; Series 455, 4-20 mA output; Series 452, 1-5 VDC output. These models can be configured with 24-standard pressure ranges from vacuum to 30,000 psi and multiple process connections from 1/4” NPT to 7/16” SAE and HF4 Autoclave high-pressure connections. Multiple electrical connections are also offered, including popular industrial and MS style connectors for easy connection. Series 450 offers cULus approval for ordinary location.

General Specifications*

Accuracy
including Linearity,
Hysteresis and Repeatability:
at 75°F, Typical
±0.1% of Calibrated FSO (Option [–A1])
±0.25% of Calibrated FSO (Standard)
±0.5% of Calibrated FSO (Vacuum only [-23])
Temperature Shift:Zero & Span: 0.0125% Per °F over the compensated temperature range
Long Term
Stability:closure rating:

±0.2% FSO /year of calibration curve
Typical Life Cycle:100 million cycles
Proof Pressure:2X range for up to 7500 psi models
1.5X range for 7500 - 30000 psi models
Input:
H455:
455*:
452*:

Excitation voltage: 9 to 30 VDC
Excitation voltage: 9 to 30 VDC
Excitation voltage: 12 to 30 VDC
* (SELV, PELV), Class II Power Supply
Supply Current:

H455 & 455:

452:


20mA max.

20mA max.
Output:
H455:



455:



452:

Output: 4–20 mA with HART® Protocol
Full Scale Output: 20 mA ±1%
Zero output: 4 mA ±1%

Output: 4–20 mA
Full Scale Output: 20 mA ±1%
Zero output: 4 mA ± 1%

Output: 1–5 VDC
Full scale output: 5.0 VDC ± 1%
Zero output: 1.0 VDC ± 1%
Dynamic
Response Time:
H455:
455 & 452:


<70 milliseconds
<50 milliseconds
Enclosure:All welded 300 series stainless steel. IP66 & IP67
and NEMA 4X rated. 316 Stainless Steel (optional)
Wetted Parts:
Sensor:




Fitting:

17-4 PH Stainless steel (more than 10k psi)
316L Stainless steel (up to 10k psi)
Inconel (optional: up to 10k psi)
17-4 PH Stainless Steel for -UL option (10k psi)

17-4 PH Stainless steel (all ranges)
316L Stainless steel and 718 Inconel (optional: up to
10k psi)
Media
General:

Corrosive and Acidic:
(up to 10,000 psi)

Gas, vapor, liquid and viscous fluids [-Z17]

718 Inconel wetted material, NACE [-NC]; and 316L
Stainless Steel, NACE [-SS]
Pressure Connection:
13 available options. Refer to product configurator
for available connections and ranges.
Electrical Connection:3 conductors for voltage output series and 2
conductors for current output series, 18 AWG, 80”
(2 m) long with integral strain relief and case ground
(standard). Jacketed cable (optional). Halogen free
wires and cable.
Temperature Ranges:
Operating (Ambient):
Compensated:
Media:
Storage:

-40 to +176 °F (-40 to +80 °C)
0 to +165 °F (-18 to +74 °C)
-40 to +176 °F (-40 to +80 °C)
-40 to +185 °F (-40 to +85 °C)
Vibration:10 g’s, 10-500 Hz, MIL-STD 202, Method 204, Cond. A
Shock:50 g’s, 11 mS, MIL-STD 202 Method 213, Cond. G.

Approvals:
cULus:


cULus approved for ordinary locations
(UL 61010-1)
HART® Protocol:

Turndown Ratio:

Analog Output
Calibration:



Sensor Trim:

Diagnostics:
HART® 7.6

10:1 (Full scale output rangeability)


Adjustable zero and span of 4-20mA.
Full scale range must be ? (calibrated
span / 10)

Sensor zero and full scale trim

Transmitter failure indicated by off-scale
analog signals to alarm the user

See HART Installation and Operation
Manual 272438 for detailed information
Compliances:CE, CRN (refer to drawing # 272479 for applicable models)
NACE (316L SS or 718 Inconel wetted material)
Electromagnetic
Compatibility (EMC)
IEC/EN 55011:


IEC/EN 61000-4-2:


IEC/EN 61000-4-3:

IEC/EN 61000-4-4:

H455:

455 & 452:


IEC/EN 61000-4-5:
H455:


455 & 452:


IEC/EN 61000-4-6:


Emission & radiated emission for class A
limits

Electrostatic discharge (ESD) test - contact
discharge +/-4 kV, Air discharge +/-8 kV

Radiated RF, EM field immunity
80mhz-1ghz, 3v/M

EFT (Burst) Test, +/-2 kV

EFT (Burst) Test, +/-1 kV



Surge Test, +/-1kV between
line and earth ground

Surge test not applicable; Class II power
supply used at input of the device

RF Immunity, 150 kHz – 80 MHz, 3V
Weight:16 Ounces (453 grams)
Warranty:1 year warranty