Smart performance with innovative and ever-strong coil module even under harsh working environments

Features

- Easy and quick auto-calibration
- Detecting RA (reverse acting) or DA (direct acting) automatically
regardless of wrong air connections
- Providing error messages against performance failures
- Possible to test the actuator with any fixed signal under a test mode
- Wide operating temperature range -30 ~ +80?
- Low air consumption

Option

- Output position transmitter (4 - 20 mA)
- 2 x alarm limit or micro switch (SPDT)
- Explosion proof type (Exia IIC T6)
- HART communication
- Profibus communication

Specifications

Input Signal

4 - 20 mA @ 24 VDC

Min. / Max. Current

3.6 mA / 50mA

Voltage Drop (Resistance)
Without Hart : 8.7 VDC (435? @ 20mA)
With Hart : 9.4 VDC (470? @ 20mA)

Stroke

Linear type : 30 - 300mm

Air Supply Pressure

1.4 - 7.0 bar (20 - 100 psi)

Output Pressure Range

0 - 100% of supply air pressure

Air Capacity

80 ?/min = 4.8 Nm3/h = 2.8 scfm (Sup = 1.4 bar)
233 ?/min = 14 Nm3/h = 8.2 scfm (Sup = 6 bar)

Air Consumption

2.8 ?/min = 0.17 Nm3/h = 0.1 scfm (Sup = 1.4 ~ 6 bar)
Performance Characteristic

Linearity < ±0.3% F.S
Sensitivity < 0.2% F.S
Hysteresis < 0.2% F.S
Repeatability < 0.2% F.S

LCD Indication

4-digit LCD indicator

Adjustable Speed

1 - 1000 ( lowest 1, highest 1000 )

Scan Time

2ms

Shut-off Value
Range 0 - 10% of position signal

Valve Action

Direct action(DA) / reverse action(RA)

Operating Temperature

-30 ~ +80? (-22 ~ +176?) **

Pneumatic Connections

Rc 1/4 or 1/4 NPT

Electrical Connections

2 x G 1/2 or 1/2 NPT

Protection Class

Other Suggested Products