Preciseness: | ±0,2 Vol. % O2 after balancing on air value 21 % O2 (with Lambda-probe LS1) |
Setting time: | <20 s on 90 % of final value (T90) (with Lambda probe LS1 type 650 R 0001 and 450 mm MEV) |
Failure impact Deviation by temperature | 1 % of measurement value / 10 K housing temperature Lambda probe LS1, temperature compensation optional |
Failure impact Deviation by pressure | 1,3 % of measurement value / 10 mbar pressure change / pressure compensation optional |
Ambient temperature - operation - transport and storage | 0°C...+60°C -40°C...+85°C |
Supply voltage | 230V AC and 115 V AC +10% / -15%, 48Hz...62Hz To be used in grounded network lines only! |
Resolution | 0,01% over the whole range |
Time for being ready with LS1 | 1...2 hours after "POWER ON" |
Approvals: | SIL 1 Confirmation: - DIN EN 61508:2011, part 1-7
|