What are you looking for?

Lamtec LT1 On Mounting Plate

BRAND : Lamtec

Details

Preciseness:±0,2 Vol. % O2 after balancing on air value 21 % O2
(with Lambda-probe LS1)
Setting time:<20 s on 90 % of final value (T90)
(with Lambda probe LS1 type 650 R 0001 and 450 mm MEV)
Failure impact
Deviation by temperature

1 % of measurement value / 10 K housing temperature Lambda probe LS1,
temperature compensation optional

Failure impact
Deviation by pressure
1,3 % of measurement value / 10 mbar pressure change / pressure compensation optional
Ambient temperature
- operation
- transport and storage

0°C...+60°C
-40°C...+85°C

Supply voltage230V AC and 115 V AC
+10% / -15%, 48Hz...62Hz
To be used in grounded network lines only!
Resolution0,01% over the whole range
Time for being ready with LS11...2 hours after "POWER ON"

Approvals:

SIL 1 Confirmation:

  • DIN EN 61508:2011, part 1-7