- Measuring ranges: -100 to +100 mbar up to -1 to +25 bar relative, 0 to 600 mbar to 0 to 25 bar absolute
- For relative pressure, absolute pressure, and filling level
- Impervious to aggressive and abrasive gases, vapors, and liquids
- Temperature of medium: -40 to +120 °C
- Linearity: ? 0.1 % of end value
- Excellent long-term stability of < 0.1 % per year
- Excellent temperature compensation
- Operation on site or using HART protocol
- Signaling if the measuring range is exceeded or not met and in the event of sensor exceedance and sensor faults
Visible on the display
- Pressure in 13 different units; measured value in % or scaled with a choice of measuring unit
- Output current in mA
- Sensor temperature in °C or °F
- Measured value error, measured value outside of measuring range
- Minimum pressure and maximum pressure (drag indicator)
- Pressure and sensor temperature can be displayed simultaneously
Settings via the operating keys
- Zero point correction
- Start and end of measuring without pressure specification (blind setting) or with pressure specification: simple, time-saving, convenient
- Attenuation
- Current generator function
- Output signal in event of fault: adjustable to 3.85 mA or 21.5 mA
- Lock function for keys
- Reset function for minimum and maximum measured values (drag indicator)
- Density correction for various measuring media
- Measuring units for pressure and temperature
Customer benefits
Applications
- Water and wastewater technology
- Paper production
- Oil and gas industry
- Power stations
- Chemical and petrochemical industries
- Food and beverage industry
- Pharmaceutical industry