- Input voltage value
- for “0” signal
- for “1” signal
|
Details
Number of inputs | 32 | Isolation (from backplane bus) In groups of | Yes (optocoupler) 16 | - Input voltage value
- for “0” signal
- for “1” signal
| DC 24 V -3 ... +5 V +13 ... +30 V | - Input current for “1” signal typ.
| 7 mA | Delay time typ. | 1.2 ... 4.8 ms | Connection of 2-wire initiator Perm. quiescent current for ”0” signal max. | Yes 1.5 mA | - Cable length unshielded max.
- shielded max.
| 600 m 1000 m | - Current consumption internal (backplane bus) typ.
- external (from +24 V) max.
| 30 mA 290 mA | Power loss (rated operation) typ. | 6.8 W | Front connector | 40-way | Ambient temperature Transport and storage temperature | 0 °C ... 60 °C -25 °C ... 75 °C |