Details
The type 8517 control unit replaces the existing control units of type 8512. The type 8517 can be used for drives drawing a current of Imax = 5 A.
Technical data
|
Dimensions
|
WxHxD 55/78/112 mm
|
Housing
|
ABS/V-0 grey
|
Attachment
|
Two holes in accordance with DIN
|
|
43604 or a standard carrying rail in
|
|
accordance with DIN EN 50022
|
Type of protection
|
Housing: IP 10; terminals: IP 20
|
Ambienttemperature
|
-20°C to +70°C
|
Fuse
|
as required (standard 2A, max. 5A)
|
Control buttons
|
2 (for On and
O?)
|
Motor contact loading
|
max. AC 250
V; 5.0 A
|
Message
|
2 LEDs,
|
Colours
|
red, yellow, green according to the
|
Standard
|
order details
|
Reporting
contacts
|
»ON«
= red, »OFF = green, per 1
|
|
zero-potential contacts can be
|
|
switch as make or break type for
|
|
»ON« and »OFF« respectively
|
|
U ? AC 250
V; I ? 2 A; P ? 500 VA
|
Remote operation
|
|
connection
|
|
Current drawn
|
approx. 250
mW
|
Remote operation
|
DC 24 V (19 - 34 V)
|
voltage
|
DC 60 V (38
- 86 V)
|
|
DC 110 V (88 -120 V)
|
Test voltage
|
Field side against reporting contacts
|
|
and field side against actuation side
|
|
4
kVe? (1
minute)
|
Ordering information
|
Type
|
Part No.
|
8517, 24 V DC remote
|
310110
|
action
|
|
8517, 60 V DC remote
|
310111
|
action
|
|
8517, 110 V DC remote
|
310112
|
action
|
|