Drive | Swiss drive inside |
For air conditioning units up to (kW) | 10 |
Pump module (L x W x H in mm) | 77 × 37,5 × 62 |
Electrical data | 230 V, 50/60 Hz, 8 W |
Power consumption in Standby mode (W) | Operation 8, Standby 1 |
Float module (L x W x H in mm) | 82 × 39 × 39 |
Max. delivery volume (l/h) | 10 |
Max. delivery height (m) | 10 |
Max. head height (m) | 1,5 |
Alarm circuit | max. 230 V, 8 A (ohmic load) NO/NC normally open/normally closed |
Special feature | Impervious to blockage or contamination due to unique valve design and large piston bore |
Switching points (mm) | Alarm: max. 23 Start: 20 ±1 Stop: 15 ±1 |